PowerGuard 400/115 VAC AC-AC Military Inverter
PowerGuard 400/115 VAC AC-AC military inverter is designed by TEDEG Defence to deliver high-reliability power conversion for defence platforms, mobile field operations and critical infrastructure in a single rugged platform. It converts 3-phase 400 VAC 50/60 Hz input power into the 3-phase 115 VAC 50 Hz output required by military avionics and special-purpose motor equipment, while supplying simultaneous loads through four independent outputs with a total capacity of 10 kVA.
Information Form
- Description
- Additional information
Description
PowerGuard 400/115 VAC AC-AC Military Inverter – Uninterrupted and Reliable Energy
PowerGuard 400/115 VAC AC-AC military inverter is designed by TEDEG Defence to deliver high-reliability power conversion for defence platforms, mobile field operations and critical infrastructure in a single rugged platform. It converts 3-phase 400 VAC 50/60 Hz input power into the 3-phase 115 VAC 50 Hz output required by military avionics and special-purpose motor equipment, while supplying simultaneous loads through four independent outputs with a total capacity of 10 kVA.
With MIL-STD-1399B technical standard compliance, MIL-STD-810G environmental durability and MIL-STD-461G EMI/EMC design criteria, PowerGuard provides stable and secure energy from forward operating bases to data centres, test laboratories and mobile command-control vehicles. Developed with local TEDEG engineering capability, PowerGuard stands out with high energy efficiency (>= 85%), an advanced protection architecture and Ethernet-based remote monitoring and control.
Product Overview
PowerGuard 400/115 VAC is a military static inverter that meets the power-conversion needs of modern defence platforms and industrial critical systems in one enclosure. Its rugged metal cabinet, dedicated colour-coded controls, dual OLED information/fault screens and Ethernet-based remote management interface provide a practical operating experience in the field.
The galvanically isolated output transformer separates the load side from grid noise, transient overvoltage and phase imbalance. This is essential for sensitive calibration equipment, military electronics, avionics benches and data-centre backup power chains where measurement accuracy and equipment lifetime matter.
Who Chooses PowerGuard?
- Defence industry integrators and prime contractors
- Military procurement units and technical service teams
- Aviation and naval avionics test centres
- Mobile command-control and communication vehicle manufacturers
- Data-centre and telecom infrastructure operators
- Test and calibration laboratories
- Emergency, disaster-management and critical-facility teams
7 Key Advantages of PowerGuard
1. Full Military Standard Compliance
PowerGuard is engineered and tested around MIL-STD-1399B, MIL-STD-810G and MIL-STD-461G requirements, making it a true defence-grade power system rather than a conventional AC-AC converter.
2. 10 kVA Total Capacity and 4 Independent Outputs
Different load profiles can be supplied simultaneously from one device: a 3.6 kVA 3-phase main output, a 2.4 kVA 3-phase output and two 2 kVA 2-phase auxiliary outputs.
3. High Overload Endurance
The unit sustains 125% load for 5 minutes, 200% for 5 seconds and 250% instantaneous load for 1 second at 0.8 power factor, supporting motor starts and short transient demands.
4. Galvanic Isolation with Output Transformer
The isolation transformer prevents harmonics, impulses and common-mode noise from being transferred to sensitive loads, improving measurement accuracy and equipment life.
5. Three-Layer Protection Architecture
Overload, short-circuit and over-temperature events are detected and logged through the OLED fault display and Ethernet-based remote interface.
6. Ethernet Remote Monitoring and Control
Through the KN6 Ethernet port, operators can monitor phase voltages, currents, output status and fault records in real time while controlling outputs remotely.
7. Mechanical Structure for Field Conditions
The 160 kg rugged metal enclosure includes steel hinges, locked doors, lifting points, emergency stop, high-voltage labels and ventilation louvers for field-safe operation.
Applications
- Forward operating base and military camp power supply
- Mobile command-control vehicles
- Special military motors for defence and aviation platforms
- Field maintenance workshops and calibration benches
- Helicopter and land-vehicle ground support equipment (GSE)
- Test and calibration laboratories
- Heavy industry and automation systems
- Imported 115 VAC machinery operated from local 400 VAC infrastructure
- Data centres, telecom sites and emergency response zones
Mechanical Features and Dimensions
PowerGuard is designed for ergonomic field transport and installation. The front face includes OLED information and fault displays, colour-coded output controls, an emergency stop button, high-voltage warning labels and the TEDEG product label. Side and rear surfaces include ventilation louvers, connection covers and lifting/handling points.
| Dimension | Value |
|---|---|
| Base | 660 ? 528 mm |
| Front (Height ? Width) | 774 ? 636 mm (600 mm cabinet width) |
| Side | 747 ? 584 mm |
| Weight | 160 ? 5 kg |
| IP Class | Suitable for outdoor use, resistant to rain and water splash |
| Colour | NATO green / military camouflage compatible |
Electrical Interface and Connector Scheme
- KN1 power input: CA3102E22-22PB (70A), R/S/T/N phases and PE body ground
- KN2 115 V 3-phase output 1: 24WE6SN, 3.6 kVA
- KN3 115 V 3-phase output 2: 24WE6SA, 2.4 kVA
- KN4 and KN5 115 V 2-phase outputs: 24WD5SN / 24WD5SA, 2 kVA + 2 kVA
- KN6 Ethernet communication: 24WC35SN with active Tx/Rx pairs and spare lines
Remote Monitoring and Control
PowerGuard provides remote observability as standard through the Transformer Ethernet Test and Monitoring software. Users can connect to the device IP, monitor R/S/T input voltages, L1/L2/L3 currents, output measurements and fault logs, and send unit-level on/off or emergency commands from the desktop interface.
Built-In Test (BIT)
The built-in test routine checks internal board health, sensor values and communication lines when required. Results are shown on the OLED fault display and can be transmitted as a fault list over Ethernet, reducing field troubleshooting time.
Efficiency and Energy Savings
With at least 85% efficiency, PowerGuard helps reduce generator fuel consumption and thermal load. Its isolated topology keeps reactive behaviour stable in generator island mode and grid-connected critical infrastructure.
PowerGuard 400 vs. Standard Industrial Isolation Transformer
| Criteria | PowerGuard 400/115 VAC | Standard Industrial Transformer |
|---|---|---|
| Military Standards | MIL-STD-1399B / 810G / 461G | Not available |
| Operating Temperature | -30 ?C / +50 ?C | Typical 0 ?C / +40 ?C |
| Dust, Humidity and Shock Resistance | Full MIL-STD-810G profile | Limited |
| EMI/EMC | MIL-STD-461G compliant | Typical EN 61000 class |
| Connector Type | MIL-DTL-38999 / 5015 | Terminal block / cable |
| Remote Management | Ethernet + desktop software | None / optional |
| Built-In Test | Available | Not available |
| Overload Profile | Up to 250% for 1 s | Typical 110% |
| Field Use | Outdoor, portable | Fixed, indoor |
Frequently Asked Questions
What does the PowerGuard 400/115 VAC AC-AC inverter do?
PowerGuard converts 3-phase 400 VAC 50/60 Hz grid or generator power into isolated 3-phase 115 VAC 50 Hz power required by military and special equipment.
Which military standards does it meet?
The unit is designed around MIL-STD-1399B, MIL-STD-810G and MIL-STD-461G requirements.
Can the device be switched on and off remotely?
Yes. Through the KN6 Ethernet port and desktop software, each output can be monitored and controlled independently.
Is it suitable for outdoor operation?
Yes. The product is designed for outdoor use and resistant to rain, splash, dust, humidity, vibration and shock according to the relevant environmental design targets.
Is it manufactured in Turkey?
Yes. PowerGuard is developed and manufactured by TEDEG Defence engineering teams in Ankara.
Request a Quote
Contact the TEDEG Defence sales team for technical consultation, project-specific configuration, quotation and delivery schedule information for the PowerGuard 400/115 VAC AC-AC military inverter.
Additional information
| Input Voltage and Frequency | 3-phase, 400 VAC, 50 Hz / 60 Hz |
|---|---|
| Output Voltage and Frequency | 3-phase, 115 VAC, 50 Hz |
| Total Power Capacity | 10 kVA |
| KN2 Output | 115 VAC, 3-phase, 3.6 kVA |
| KN3 Output | 115 VAC, 3-phase, 2.4 kVA |
| KN4 Output | 115 VAC, 2-phase, 2 kVA |
| KN5 Output | 115 VAC, 2-phase, 2 kVA |
| Overload Capacity | 125 percent for 5 min / 200 percent for 5 s / 250 percent for 1 s @ 0.8 PF |
| Efficiency | At least 85 percent |
| Output Isolation | Isolated output transformer with high-voltage insulation |
| Protection Mechanisms | Overload, short-circuit and over-temperature protection |
| Operating Temperature | -30 °C to +50 °C |
| Operating Environment | Indoor and outdoor operation |
| Electrical Interface | MIL-DTL-38999 and MIL-DTL-5015 military connectors |
| Communication Interface | Ethernet (KN6) for remote monitoring and on/off control |
| Visual Interface | OLED information screen + OLED fault screen |
| User Interface | Dedicated colour-coded buttons for each output, emergency stop |
| Weight | 160 ± 5 kg |
| Mechanical Dimensions | 660 x 528 mm base / 636 x 774 mm front / 584 x 747 mm side |
| Part Number | TDG-PFC-A0000 |
TECHNICAL DOCUMENT - EN
PowerGuard 400/115 VAC AC-AC Military Inverter
Additional information
| Input Voltage and Frequency | 3-phase, 400 VAC, 50 Hz / 60 Hz |
|---|---|
| Output Voltage and Frequency | 3-phase, 115 VAC, 50 Hz |
| Total Power Capacity | 10 kVA |
| KN2 Output | 115 VAC, 3-phase, 3.6 kVA |
| KN3 Output | 115 VAC, 3-phase, 2.4 kVA |
| KN4 Output | 115 VAC, 2-phase, 2 kVA |
| KN5 Output | 115 VAC, 2-phase, 2 kVA |
| Overload Capacity | 125 percent for 5 min / 200 percent for 5 s / 250 percent for 1 s @ 0.8 PF |
| Efficiency | At least 85 percent |
| Output Isolation | Isolated output transformer with high-voltage insulation |
| Protection Mechanisms | Overload, short-circuit and over-temperature protection |
| Operating Temperature | -30 °C to +50 °C |
| Operating Environment | Indoor and outdoor operation |
| Electrical Interface | MIL-DTL-38999 and MIL-DTL-5015 military connectors |
| Communication Interface | Ethernet (KN6) for remote monitoring and on/off control |
| Visual Interface | OLED information screen + OLED fault screen |
| User Interface | Dedicated colour-coded buttons for each output, emergency stop |
| Weight | 160 ± 5 kg |
| Mechanical Dimensions | 660 x 528 mm base / 636 x 774 mm front / 584 x 747 mm side |
| Part Number | TDG-PFC-A0000 |