PDU (power distribution unit)
Takes one or more power inputs and splits them into protected, switchable outputs for equipment on a platform or in a rack.
Datasheet example: PDU-RT5002: 3 × 220 VAC 50 Hz inputs, 10 × 25 A protected AC/DC outputs, 4U 19"; TDG-EDP-D0X: (+) and (−) 400 A bus bars.
DC busbar
A rigid conductor, usually copper, that collects DC sources at one point and feeds the outputs from there; it carries more current than cable.
Datasheet example: TDG-EDP-D0X: (+) and (−) 400 A power bus bars collect the Battery 1, Battery 2, alternator and battery charger inputs.
MIDI fuse
A MIDI fuse is a bolt-down fuse: its fuse strip is screwed onto busbar or terminal studs instead of being pushed into a holder. The bolted joint suits vibration and the high currents of vehicle DC circuits, which is why MIDI fuses are common on vehicle distribution outputs.
Datasheet example: TDG-EDP-D0X: MIDI output fuses rated 100 A, 60 A and 30 A @ 28 VDC, with spare MIDI fuses from 30 A up to 200 A.
Bypass switch (PDU)
A bypass switch keeps power flowing when the protection logic of a distribution unit would otherwise cut an output after a fault or an exceeded limit. It is meant for critical moments when losing the load is worse than the fault itself, so it should be used deliberately and switched back afterwards.
Datasheet example: PDU-RT5002: with the BYPASS switch on, all faults and warnings are ignored and the system keeps supplying power; PDU-R2D4 has emergency stop and bypass buttons on its front panel.
Surge protection device (SPD)
A surge protection device diverts short overvoltage transients on a mains or generator line, such as switching surges and lightning-induced spikes, to earth before they reach the equipment. It is fitted at the input of a panel or distribution unit.
Datasheet example: PowerGuard PDU-R2D4 has an integrated SPD on the input line with LED status; the ED0 and EDX schematics of the AC power distribution panel include a surge arrester.
EMI gasket
An EMI gasket is a conductive seal fitted between a door or cover and the enclosure body. It closes the gap electrically, so the metal enclosure stays a continuous shield against electromagnetic interference, and it also seals the enclosure.
Datasheet example: TDG-EDP-D0X has an EMI gasket on the door; the AC power distribution panel has an EMI gasket on the enclosure door, together with door and body grounding.
Battery disconnect
A battery disconnect is a switch or contactor that separates the vehicle batteries from the distribution bus. It leaves the downstream wiring de-energised for maintenance and lets the crew isolate the batteries quickly in an emergency.
Datasheet example: TDG-EDP-D0X has a battery disconnect and an emergency stop button; its input contactor opens below 21 VDC and disconnects the batteries from the system.
A contactor is a power switch operated by a coil, so a low-current control signal can open or close a high-current circuit. In a distribution unit the input contactor connects the source to the bus, while a load contactor switches a group of outputs on or off.
Datasheet example: TDG-EDP-D0X: the input contactor closes above 21.5 VDC and opens below 21 VDC, also opening the load contactor; the emergency stop opens both. MAR-2 manages its outputs centrally through contactors K1 and K2.
ATS (automatic transfer switch)
Switches the load to the next source in a set priority order when the active source fails, without operator action.
Datasheet example: PDU-RT5002: UPS, mains and generator inputs (3 × 220 VAC); mains is the primary source, with transfer to generator when necessary.
Mains–generator selection panel
A panel on which the operator selects one of two AC sources, mains or generator, by hand and distributes it to output groups. Unlike an ATS, the changeover is manual.
Datasheet example: MAR-2: 220 VAC 50 Hz mains/generator input, manual AC source selector, 9 × 220 VAC outputs.
19-inch rack and rack unit (U)
The standard cabinet width for mounting equipment; height is counted in rack units (U), so a 4U unit is four times as tall as a 1U unit.
Datasheet example: PDU-RT5002: 4U, 19" rack; PDU-R2D4: 2U, 19″, 482.6 mm front panel.